Specifications
AS-Interface slaves
Motor starters for operation in the field, high degree of protection
SIRIUS M200D motor starters
M200D motor starters for AS-Interface
6/99
Siemens IK PI · 2012
6
■
Overview (continued)
✓ Function is available.
-- Function not available.
1)
The data records are a reduced selection compared with
PROFIBUS/PROFINET.
SIRIUS M200D SIRIUS M200D
AS-i Basic AS-i Standard
Device functions (firmware features)
Slave on the bus
Fieldbus
✓ AS-i
Slave type
✓ A/B acc. to Spec 2.1 ✓ A/B acc. to Spec 3.0
Profile
✓ 7.A.E ✓ 7.A.E & 7.A.5
Number of assigned AS-i addresses on the bus
✓ 1 ✓ 2
Number of stations per AS-i master
✓ Maximum 62 devices ✓ Maximum 31 devices
AS-i master profile
✓ M3 and higher ✓ M4 and higher
Parameterization
DIP switches
✓ --
Potentiometer for rated operational current ✓ --
ES Motor Starter -- ✓
Data records through AS-i -- ✓
Diagnostics
Diagnostics through parameter channel
✓
Acyclic through data records -- ✓
Expanded process image PAE 4 bytes -- ✓
Process image
Process image
✓ 4I/3O ✓ 6I/4O
Data channels
Local optical interface (manual local)
✓
AS-i bus ✓
Motor Starter ES through local interface -- ✓
Motor Starter ES through bus --
Data records
1)
(acyclic)
Parameterization
-- ✓
Diagnostics -- ✓
Measured values -- ✓
Statistics -- ✓
Commands -- ✓
Inputs
Number
✓ 4
• of these in the process image
✓ 2 through AS-i ✓ 4 through AS-i
Input action
✓ Permanently assigned functions, see manual ✓ Parameterizable: Flexible
Quick-Stop
✓ Permanent function: latching, edge-triggered ✓ Parameterizable function: latching
(edge-triggered), non-latching (level-triggered)
Outputs
Number
✓ 1
Output action
✓ Permanent function: assigned with group fault ✓ Parameterizable: Function, see manual
Brake output
180 V DC/ 230/400 V AC / none
✓
Motor protection
Overload protection
✓ Electronic, wide range 1:10
Short-circuit protection
✓
Full motor protection ✓
Temperature sensor ✓ Parameterizable using DIP switches:
PTC or Thermoclick or deactivated
✓ Parameterizable using ES Motor Starter, data
record: PTC or Thermoclick or deactivated