Specifications

AS-Interface
System components and accessories
Extension plug
6/140
Siemens IK PI · 2012
6
Overview
AS-Interface extension plug (on AS-Interface M12 feeder)
With the extension plug/extension plug plus it is possible to
double the cable length possible in an AS-Interface segment
from 100 to 200 m.
The extension plug is a passive component, the extension plug
plus is equipped in addition with an A/B slave.
The extension plug / extension plug plus has an M12 plug and
can be connected with it to the AS-Interface M12 feeder with
degree of protection IP67. Only one power supply unit is needed
to supply power to the slaves on the up to 200 m long segment.
Design of an AS-Interface segment with an extension plug
To construct an AS-Interface segment with a cable length of
more than 100 m and up to a maximum of 200 m, the extension
plug or extension plug plus is installed at that point of the net-
work which in a range of approx. ±10 m is furthest from the
AS-Interface power supply unit. The extension plug is not al-
lowed to be used in AS-Interface networks smaller than 100 m.
As with all AS-Interface networks, any network structure (line,
tree, star) is possible when using the extension plug/extension
plug plus. Only one extension plug/extension plug plus is
required per 200 m segment even with a tree or star structure.
Note:
The AS-Interface extension plug and the extension plug plus are
not suitable for AS-i Power24V networks. Both are recom-
mended for use in AS-Interface networks with AS-Interface
power supply units (e.g. 3RX9 501-0BA00).
Maximum network size with repeaters and extension plug (master at center of network)
Selection and ordering data
1)
For connection to the AS-Interface flat cable you need the AS-Interface
M12 feeder, which must be ordered separately, see section "Accessories".
Version Order No.
3RK1 901-1MX00
AS-Interface extension plug
1)
• Doubling of the cable length to 200 m per AS-Interface segment
• Undervoltage monitoring signal by means of diagnostics LED
3RK1 901-1MX00
AS-Interface extension plug plus
1)
• Doubling of the cable length to 200 m per AS-Interface segment
• Undervoltage monitoring signal through integrated AS-Interface slave to
AS-Interface master
3RK1 901-1MX01
Accessories
3RX9 801-0AA00
AS-Interface M12 feeders
• For adaptation of shaped AS-Interface cable to a standard round cable
• Insulation piercing method for connection of AS-Interface cable
• M12 socket for connection of standard round cable
• Degree of protection IP67
3RX9 801-0AA00
3RK1 901-1NR10
AS-Interface M12 feeders
• Transition of AS-Interface cable without U
aux
, with M12 socket
• Insulation piercing method for connection of AS-Interface cable
• M12 socket for connection of standard round cable
•Max. 4A
• Degree of protection IP67/IP68/IP69K
3RK1 901-1NR10
200 m
600 m
200 m 200 m
Repeater
Master
Slave
Power
supply
Slave Slave Slave Slave Slave
Power
supply
Power
supply
Extension
plug
Extension
plug
Extension
plug
Repeater
NSA0_00371b
Kap_06_en.book Seite 140 Freitag, 2. September 2011 1:42 13
© Siemens AG 2011