Specifications

AS-Interface slaves
Motor starters for operation in the field, high degree of protection
SIRIUS MCU motor starters
General data
6/108
Siemens IK PI · 2012
6
Overview (continued)
Function is available
-- Function not available.
3RK43 20-3.R51-.BA0 3RK43 20-3.Q54-.BA. 3RK43 20-5.Q64-.BA.
Type SIRIUS MCU motor starters for AS-Interface
Plastic enclosures Metal enclosures Metal enclosures
Electromechanical
Switching
Electromechanical
Switching
Electronic
Switching
Device functions (software features)
Slave on the bus
Fieldbus
AS-i
Bus connection
M12
Slave type
AS-i Spec 2.0 A/B acc. to Spec 2.1
AS-i Slave Profile IO.ID.ID2
3.0.F 7.A.E
Number of assigned
AS-i addresses on the bus
1
Number of stations
Maximum 31 devices Maximum 62 devices
Diagnostics
LEDs
Process image
Process image
2I/2O 4I/3O
Data channels
Manual local operation
--
Inputs
Number
1 2
• of these in the process image
DI1 DI2 / DI3
Connection
Screw terminal, internal M12 – A coded
Input signal
Switching contact
or 2-wire Bero
Switching contact or
2/3-wire Bero
Input level
AS-i +
Outputs
Number
1 on the direct-on-line starter
0 on the reversing starter
1
• of these in the process image
DO1 DO2
Connection
Screw terminal, internal M12 – A coded
Output level
Relay contact, floating AUX-PWR+ (24 V DC)
Motor protection
Overload protection
Thermal
overload releases
Electronic
overload releases
Wide range
Short-circuit protection
Auto-RESET
--
Temperature sensor -- TC (Thermoclick)
Device functions
Response when
repair switch is tripped
Signal through AS-i
Plug monitoring
-- Possible (with plug option)
Kap_06_en.book Seite 108 Freitag, 2. September 2011 1:42 13