Specifications

AS-Interface slaves
Motor starters for operation in the field, high degree of protection
SIRIUS M200D motor starters
M200D motor starters for AS-Interface
6/100
Siemens IK PI · 2012
6
Overview (continued)
Function is available.
-- Function not available.
Application
The M200D AS-i standard is particularly suitable for highly auto-
mated applications in conveyor systems, which require that de-
vices and plants be monitored to prevent or limit plant downtime.
The option of planning the functions of the motor starter or its in-
terfaces also makes fine-adjustment to the function of the motor
starter in the application possible and hence, provides for ex-
treme flexibility.
SIRIUS M200D SIRIUS M200D
AS-i Basic AS-i Standard
Device functions (firmware features)
Device functions
Repair switch
Current limit monitoring bottom -- Parameterizable
Current limit monitoring top
-- Parameterizable
Zero current detection
Permanent function: disconnection, less than
18.75 % of the rated operational current I
e
Parameterizable
Blocking current
Permanent function: Starting up of the motor:
tripping limit at 800 % of the rated operational
current I
e
for 10 s
Active operation: Threshold for tripping
"blocking current" at 400 % of the rated
operational current I
e
Parameterizable
Unbalance
Permanent function: at 30 % of the rated
operational current I
e
(only mechanical MS)
Parameterizable
Load type
Permanent function: 3-phase Parameterizable: 1- and 3-phase
Shutdown class
Parameterizable using DIP switches:
CLASS 10/deactivated
Parameterizable using ES Motor Starter,
data record: CLASS 5, 10, 15, 20
Protection against voltage failure
Parameterizable: Activated/deactivated
Soft starter control function
Soft start function
-- Only electronic version
Bypass function
-- Only electronic version
Kap_06_en.book Seite 100 Freitag, 2. September 2011 1:42 13