Technical Information FR - FC - FCO - FCR Models100÷800 FR - FC - FCO - FCR 100÷800 Fan coil units series
FAN COIL UNITS SERIES FR - FC - FCO - FCR Models 100-200-300-400-600-800 Technical details This manual is in three sections: - SECTION A - GENERAL INFORMATION Contains descriptions and technical details of the equipment. - SECTION B - INSTALLATION DETAILS FOR THE INSTALLER Contains all the instructions and notes necessary for installing equipment.
1.7 1.8 1.9 1.10 1.11 1.12 Measurements ........................................................................................................................ 6 Components ........................................................................................................................... 8 Technical data tables ............................................................................................................ 13 Standard 3 row battery heat output diagrams .................................
SECTION A - GENERAL INFORMATION 1. PRINCIPAL CHARACTERISTICS 1.4 ASSEMBLY CHARACTERISTICS 1.1 APPLIANCE CLASSIFICATION 1.4.1 Available versions The F-FR-FC-FCR fan heaters are defined as "air treatment terminals for winter and summer air conditioning". 1.2 EC CONFORMITY - CERTIFICATION The EC symbol guarantees that the appliance conforms to EEC machinery directive EEC/98/ 37, low tension directive EEC/73/23, electromagnetic directive EEC/89/336 and any subsequent amendments.
The single-phase 230 V electric motors have a permanently installed capacitor and heat protection is incorporated. Use of the autotransformer means that 6 speeds can be accessed. Three are standard and can be selected from the control panel. The motor is directly coupled to the fan(s) and mounted on a flexible support and the system is assembled to include a tray for collection of condensation. Electrical connection with the control panel is by rapid polarised insert.
- Electronic thermostat 1 (with bracket for mounting on the appliance or on the wall). - 90° air intake system for FC - FCR versions with casing. - Electronic thermostat 2 (with bracket for mounting on the appliance or on the wall). - 90° air output system for FC - FCR versions with casing. - Microprocessor thermostat (with bracket for mounting on the appliance or on the wall). - Direct air output system for FC -FCR versions with casing. - Mechanical thermostat for base control panel 2.
1.7 SIZE AND MASS 1/2” G entry 144 45 93 274 477 562 360 1/2” G exit 150 220 172 48 C A D B 562 VERTICAL FR VERSION WITH COVER A 477 D 45 144 220 172 48 274 B 1/2” G exit 1/2” G entry Fig. 1 HORIZONTAL FC VERSION WITH COVER Mod. 100 200 300 400 600 800 A 760 870 980 1.090 1.310 1.310 B 440 550 660 770 990 990 C 460 570 680 790 1.010 1.010 D 644 754 864 974 1.194 1.194 pag.
1.7 SIZE AND MASS 1/2” G entry 144 45 274 477 525 1/2” G exit 220 142 A B VERTICAL FC VERSION WITH CASING A+60 525 24 477 A 220 118 144 45 274 B 1/2” G exit 1/2” G entry HORIZONTAL FCR VERSION WITH CASING Fig. 2 Mod. 100 200 300 400 600 800 A 480 590 700 810 1.030 1.030 B 440 550 660 770 990 990 pag.
pag. 8 Fig. 3 1.8 DETAILED VIEW - Vertical FR version with cover modd.
pag. 9 Fig. 4 1.8 DETAILED VIEW - Horizontal FC version with cover modd.
pag. 10 Fig. 5 1.8 DETAILED VIEW - Vertical FCO version with casing modd.
pag. 11 Fig. 6 1.8 DETAILED VIEW - Horizontal FCR version with casing modd.
Components Vertical FR version with cover (fig.
1.9 TECHNICAL DATA TABLE Heat potential Unit of mes. 100 200 300 400 600 800 max. 2.830 4.130 5.640 7.050 9.770 12.330 med. 2.530 3.680 5.140 6.290 8.860 11.230 min. 2.220 3.210 4.670 5.230 7.480 10.580 l/h 243 355 485 606 825 1.060 kPa 1,50 3,00 7,30 11,45 23,50 33,00 max. 1.620 2.200 3.370 4.050 5.900 6.060 med. 1.450 1.830 3.070 3.640 5.270 5.610 min. 1.270 1.680 2.790 3.240 4.620 5.090 max. 1,03 2,27 6,45 8,90 22,25 26,50 max. 1.
1.10 3 row standard battery potential heat output diagrams Rese iche - M od. Heatterm output - Mod. 100100 Le del grafico alla speed. massima conoscere rese Therese heattemiche output figures in thecorrispondono graph are for max. Tovelocità.
1.10 3 row standard battery heat potential diagrams Heattermiche output - Mod. 300 300 Rese - M od. Le del grafico alla massima conoscere rese Therese heattemiche output figures in thecorrispondono graph are for max. speed. Tovelocità.
1.10 3 row standard battery heat potential diagrams Rese iche - M 600 od. 600 Heat term output - Mod. Le rese del grafico alla speed. massima conoscere rese The heattemiche output figures in thecorrispondono graph are for max. Tovelocità.
1.
1.
1.11 Diagrams for standard 3 row battery charge loss for 10°C water To calculate charge loss at different temperatures, multiply by coefficient K °C 40 50 60 70 80 K 0,88 0,86 0,84 0,82 0,8 FR-FC-FCO-FCR 600 30 28 26 24 ∆P [kPa] 22 20 18 16 14 12 10 8 6 4 300 350 400 450 500 550 600 650 700 750 800 850 Portata Capacity[kg/h] (kg/h) FR-FC-FCO-FCR 800 40 38 36 34 32 ∆P [kPa] 30 28 26 24 22 20 18 16 14 12 10 500 550 600 650 700 750 800 Portata [kg/h] Capacity (kg/h) pag.
1.12 ELECTRICAL LAYOUT MICROPROCESSOR THERMOSTAT BASIC CONTROL PANEL 1 Check probe Fan Environment probe See table for connections summer/ winter Hot water valve Cold water valve BASIC CONTROL PANEL 2 See table for connections OFF Fan EST. INV.
1.
SECTION B - TECHNICAL NOTES FOR THE INSTALLER 2. ATTENTION 2.1 2.1 INSTALLER QUALIFICATIONS WARNING! Both the plumbing and electrical parts of the installation must be carried out by specialists, qualified under the terms of law 46/'90, who can correctly perform the operations specified in this manual. 2.
for horizontal versions FR - FCR (fig. 9). When using appropriate accessories (for example, feet or supports) follow the instructions for mounting them. 3. INSTALLATION 3.1 POSITIONING NOTES WARNING! The appliances are not designed for use in industrial processes and/or installation in places where corrosive or explosive products are used.
TAKING THE COVER APART - MODELS FR - FC A traces of water may be found under the fan heater and/or in the room. Put the plugs in the holes, leaving the screws loose. B It is advisable for two people to lift and position the fan heater in order to avoid any possible damage to the wall or to the appliance. Lift the fan heater, placing the 4 fixing points on the screws and screw into place. Turn the screws sufficiently to ensure safe mounting. 3.2.
SPACES FOR PLUMBING ATTACHMENTS (FR -FC) 70 3.2.3 Electricity connection WARNING! Turn off the power before connecting to the electricity supply and complete the plumbing connections first and ensure they are secure. 70 1/2” G entry Ensure that the electricity supply is 230V - 50Hz monophase and that there is an earth cable. The electricity supply, where a fan heater is mounted, should be protected and controlled by an adequate load (minimum 3 mm. Contact opening) omnipolar switch and a 2A - 250V fuse.
summer/winter switch (B) in the position appropriate for the cycle in course (towards the top = summer, towards the bottom = winter). - Version 2 controls: Put switch (B) in the position appropriate for = summer, = the cycle in course ( winter). b) If there is one (in the electronic or microprocessor thermostats), turn the room temperature thermostat (C) to the required temperature.
SECTION C - USER INSTRUCTION AND MAINTENANCE MANUAL 6.2 RECOMMENDATIONS - IMPROPER USE appliance - do not leave objects, containers or glasses containing liquid on the air outlet grille - do not cover the heater with curtains or any objects which could partially obstruct the intake and/or outlet of air - do not put clothes, cloths or anything to dry on the heater grille. As well as obstructing the passage of air, any dripping inside the appliance could cause electric shock.
those parts. - do not remove the filter without first disconnecting the electricity supply and allowing the internal parts to cool. - in places where it is advisable to block access to the control panel (public places, schools etc.), the flaps in version F (vertical with cover) can be blocked using the screws and screw covers provided. 7. STARTING UP - Version 1 controls Turn switch (A) to "OFF" - Version 2 controls Turn switch (B) to "OFF" 7.3.
wash the filter under running water and wait for it to dry completely before re-insertion. If the filter material starts to show signs of wear after a few periodic cleanings, it should be replaced to ensure fully effective functioning. Do not throw the old filter away carelessly, but dispose of it in an appropriate rubbish container. 8.3 POSSIBLE PROBLEMS Any repair operations should be carried out by qualified personnel. In the case of breakdown, contact the nearest Service Centre.
DECLARATION OF CONFORMITY Manufacturer: ACCORRONI S.r.l. Address: 60027 Osimo (AN) - Via Pignocco, 25 Tel. 071/723991 - Fax 071/7133153 Appliances: Fan Heaters - units for temperature control Series/Types: FR - FC - FCO - FCR Models: 100 - 200 - 300 - 400 - 600 - 800 With reference to the above appliances, Accorroni S.r.l.
pag.
Fan coil units series FR - FC - FCO - FCR - Technical details Cod. 26209501 IT - Rev.