Service manual

SC Series Boilers – Installation and Service Manual
34
Troubleshooting Guide Section 8
8.1 Possible Causes and Solutions
Problem Possible Cause Solution
No
p
ower.
Check
p
ower switches and wirin
g
.
No gas supply to boiler. Check gas source and pressure.
Gas supply pipes are not purged of air. Purge gas line.
No heat demand.
Check if thermostat setting is above room
temperature and aquastat setting is above
boiler water temperature.
Flow switch or low water cut off.
Check pump capacity & flow direction.
Check for correct water levels and air locks.
Gas valve failure (closed position). Check gas valve and replace if necessary.
Faulty wiring.
Check wiring of aquastats, zone valves, and
thermostats for loose or broken wires and
repair.
Fault
y
a
q
uastat, thermostat, or zone valve.
Check and re
p
lace if necessar
y
.
Pressure switch failure or airflow blockage
in heat exchanger, venting, air inlet pipe or
termination.
Check pressure switch and replace if
necessary. Remove airflow blockages.
Boiler will not fire.
Fault
y
controller or control wirin
g
.
See "Control trouble troubleshootin
g
".
Poor flow in boiler or circulator failure.
Check pump for proper capacity & flow
direction. Replace if necessary.
Thermostat, heat anticipator, or aquastat
set too low.
Check and adjust.
Boiler oversized or insufficient radiation. Check and adjust if necessary.
Boiler goes on and off at
frequent intervals.
Wrong type of thermostat or controller. Check and replace if necessary.
Gas valve failure
(
o
p
en
p
osition
)
.
Check
g
as valve, re
p
lace if necessar
y
.
Faulty wiring.
Check wiring of aquastats, zone valves, and
thermostats for short circuits or incorrect
wiring.
Boiler fires continuously.
Fault
y
a
q
uastat, zone valve or thermostat.
Check and re
p
lace if necessar
y
.
Boiler is overheated and safety high limit
aquastat fails to cut out.
Check aquastats and adjust or replace if
necessary.
Improper wiring. Check and correct.
Foreign matter in heat exchanger. Flush heat exchanger if necessary.
Poor circulation. Check pump for correct flow.
Rumbling and moaning
sound in boiler.
Air trapped in heating system. Purge air.
Flue leakin
g
.
Check ventin
g
and boiler if leakin
g
.
Insufficient combustion air to boiler.
Check combustion and ventilation air
opening in boiler room meets installation
code requirements, and air differential
pressure if too low.
Gas odor.
Leak in gas system.
See “What to do if you smell gas” on cover.
Have gas fitter test system and repair leaks.
Burner cracked or eroded
Check & re
p
lace if necessar
y
.
Not enough combustion air or wrong air
switch setting
Adjust air shutter & check air switch
condition
Flame flash back
The vent or air inlet blocked Check & clean