Service manual

SC Series Boilers – User’s Information Manual
9
13 USER'S CHECKLIST
Reference
Section
ο
Check air openings, termination cap are not restricted and will not be blocked off.
Adequate supply air is necessary for combustion and ventilation.
8, 10
ο
Check that there are no sagging sections along the venting horizontal runs.
10
Check the tubes connecting the air differential pressure switches with the air chamber
tightly.
11
ο
Check externally the vent system for soot, rust scale or corrosion. Check for
dislodged venting or possible leaks in venting ducts and boiler.
10
Check to insure that the condensate trap is filled with water, but not plugged.
9
ο
Visually inspect main burners to ensure proper flame operating characteristics and
ignition/extinction is ok.
12
ο
Check burner operation to hear that they do not make unusual audible sounds
when boiler is on.
ο
Check that gas piping is secured. Smell for gas leaks around boiler and gas piping
connections. Gas leaks can also be checked for using a soap solution; do not use
an open flame to check for leaks. Note: Propane is heavier than air and pools in a
low area in the event of a leak.
6
ο
Visually inspect for leaks in the water piping and at water piping connections.
ο
Circulating pumps used with hot water heating systems should be inspected for
water leaks.
ο
Check for weeping at pressure relief valve outlet during normal operation.
14
ο
Listen for unusual audible sounds in the boiler.
13
ο
Read temperature and pressure gauge. Check with qualified installer or service
agency to determine acceptable temperature and pressure range for your heating
system.
ο
Combustible materials, gasoline and other flammable vapors and liquids should not
be stored in the area of the boiler.
5
If any problems are identified during your inspection, contact a qualified service agency for
corrective measures.
Once every year at the beginning of the heating season:
ο
Have a qualified service technician remove the draft hood from the boiler and inspect the flue ways for
the presence of soot or rust scale. The draft hood and smoke pipe connecting the draft hood to the flue
must be inspected for rust or corrosion before replacing the draft hood. The presence of soot, rust
scale or corrosion indicates misadjustment.
ο
Have a qualified service technician inspect the pilot burner and main burner.
ο
The qualified service technician should follow the "Maintenance Checklist" and other applicable safety
information found in the Installation and Service Manual.