Dimensions and Specifications Section 1
1.1 TECHNICAL SPECIFICATIONS
Maximum Operating Pressure: 90 p.s.i.
Maximum Operating Water Temperature: 210ºF
Water Capacity in Boiler: 6.6 US Gallons
Inlet and Outlet Pipe Size: 1 1/4” NPT
Controller Pump Switch Capacity: 5A Maximum
Table 1: Super Hot MSE Series Electric Boiler Specifications. (Flange Type Elements)
Single Phase Three Phase
Super Hot
MSE Series Electric Boilers
208 Vac 240 Vac 208 Vac 240 Vac 480 Vac 600 Vac
Model kW Btu/Hr Amp Amp Amp Amp Amp Amp
6MSE 6 20,474 28.9 25.0 16.7 14.4 7.2 5.8
9MSE 9 30,708 43.3 37.5 25.0 21.6 10.8 8.7
12MSE 12 40,848 57.7 50.0 33.3 28.8 14.4 11.5
15MSE 15 51,185 72.1 62.5 41.6 36.0 18.0 14.4
18MSE 18 61,422 86.5 75.0
54.6* 47.3* 23.7* 18.9*
20MSE 20 68,240 96.2 84.3
63.6* 55.1* 27.6* 22.0*
24MSE 24 81,895 115 100 66.5 57.7 28.8 23.1
27MSE 27 92,124 130 113 74.9 64.9 32.4 26.0
30MSE 30 102,369 144 125 83.2 72.1 36.0 28.8
34MSE 34 116,008 164 142
100* 87.0* 43.5* 34.8*
38MSE 38 129,656 183 158
118* 102* 50.5* 40.4*
42MSE 42 143,304 202 175 116 101 50.5 40.4
45MSE 45 153,540 216 188 125 108
57.7* 46.2*
48MSE 48 163,776 231 200
138* 119* 59.6* 47.7*
54MSE 54 184,248 260 225 150 130 64.9 52.0
Note:
1. Other models of the MSE Series Electric Boiler may be available subject to inquiry.
2. * Delta connection (unbalanced load) amperage of high leg indicated.
3. Approximate shipping weights:
Model Weight
Ŧ
6MSE & 9MSE 114 lb
12MSE to 18MSE 116 lb
20MSE & 24MSE 118 lb
27MSE to 38MSE 122 lb
42MSE to 54MSE 126 lb
Ŧ
Add 45 lb for package models