Specifications
Installation
27
F232086
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Tab l e 7
Electrical Specifications
Voltage Designation Standard Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load
Amps
Breaker
AWG
mm
2
Full Load
Amps
Breaker
AWG
mm
2
35
D 220-240 50 3 3 14 25 10 3x6 38 50 6 3x16
F 440-480 60 3 3 8 15 14 3x2.5 27 30 10 3x6
G 440 50 3 3 8 15 14 3x2.5 27 30 10 3x6
H 380 60 3 3 8 15 14 3x2.5 27 30 10 3x6
M 550-575 60 3 3 8 15 14 3x2.5 Not available in this voltage.
O 208-240 60 3 3 14 25 10 3x6 48 50 6 3x16
S 380 50 3 3 8 15 14 3x2.5 27 30 10 3x6
W 380-415 50 3 3 8 15 14 3x2.5 22 30 10 3x6
60
D 220-240 50 3 3 13 30 10 3x6 66 80 3 3x30
F 440-480 60 3 3 7 20 12 3x4 33 40 8 3x10
G 440 50 3 3 7 20 12 3x4 30 40 8 3x10
H 380 60 3 3 7 20 12 3x4 26 35 8 3x10
M 550-575 60 3 3 7 20 12 3x4 Not available in this voltage.
O 208-240 60 3 3 13 30 10 3x6 66 80 3 3x30
S 380 50 3 3 7 25 10 3x6 26 35 8 3x10
W 380-415 50 3 3 7 20 12 3x4 29 40 8 3x10
NOTE: Wire sizes shown are for copper, THHN, 90° conductor per NEC article 310.