Specifications

130 Pound Capacity Models - CE Approval
Voltage Designation Specifications
Code Voltage Cycle Phase Wire
Full
Load
Amps
Circuit
Break-
er mm2
M-Speed Models
Q 220-240 50/60 3 3 17 20 2.5
N Standard 440-480 50/60 3 3 11 16 2.5
Electric Heat 74 80 16
P Standard 380-415 50/60 3 3 11 16 2.5
Electric Heat 65 80 16
V-Speed Models
Q 220-240 50/60 3 3 21 25 2.5
N Standard 440-480 50/60 3 3 12 16 2.5
Electric Heat 74 80 16
P Standard 380-415 50/60 3 3 12 16 2.5
Electric Heat 65 80 16
Wire sizing listed in this table is based on Article 310, Table 310.16 of the NEC; at 104°F [40°C] ambient temperature. Follow your
local electrical codes. Use only copper conductors, rated for 194ºF [90°C] or higher, type THHN or better. No more than three cur-
rent carrying conductors per raceway. Contact your local Authority having jurisdiction if you have questions. Circuit breakers should
be UL 489 listed or better. Single phase circuit breakers for single phase machines only; three phase circuit breakers for all others.
Table 30
Specifications and Dimensions