Specifications

130 Pound Capacity Models - North American Approval
Voltage Designation Specifications
Codes Voltage Cycle Phase Wire
Full
Load
Amps
Circuit
Break-
er *AWG *mm2
M-Speed
Q 220–240 50/60 3 3 16 20 12 4
N 440–480 50/60 3 3 10 15 14 2.5
P 380–415 50/60 3 3 10 15 14 2.5
V-Speed Models
Q 200–240 50/60 3 3 21 30 10 6
N Standard 440–480 50/60 3 3 12 15 14 2.5
Electric
Heat
74 80 4 25
P Standard 380–415 50/60 3 3 12 15 14 2.5
Electric
Heat
65 70 4 25
Wire sizing listed in this table is based on Article 310, Table 310.16 of the NEC; at 104°F [40°C] ambient temperature. Follow your
local electrical codes. Use only copper conductors, rated for 194ºF [90°C] or higher, type THHN or better. No more than three cur-
rent carrying conductors per raceway. Contact your local Authority having jurisdiction if you have questions. Circuit breakers should
be UL 489 listed or better. Single phase circuit breakers for single phase machines only; three phase circuit breakers for all others.
Table 24
Specifications and Dimensions
F8410701ENR10
©