Specifications
North American Approval
Machines can be converted for lower voltage operation and/or 50
Hz operation. Refer to conversion label by nameplate for details.
45 Pound Capacity Models - North American Approval
Voltage Designation Specifications
Codes Voltage Cycle Phase Wire
Full
Load
Amps
Circuit
Break-
er *AWG *mm2
L-Speed Models
X 200–240 50/60 1/3 2/3 8/6 15 14 2.5
M-Speed Models
X 200–240 50/60 1/3 2/3 11/8 15 14 2.5
Q 200–240 50/60 3 3 71 80 4 25.0
N Standard 440–480 50/60 3 3 5 15 14 2.5
Electric
Heat
36 40 8 10.0
P Standard 380–415 50/60 3 3 6 15 14 2.5
Electric
Heat
32 40 8 10.0
V-Speed Models
X 200–240 50/60 1/3 2/3 15/9 20/15 12/14 4.0/2.5
Q Standard 200–240 50/60 3 3 9 15 14 2.5
Electric
Heat
71 80 4 25.0
N Standard 440–480 50/60 3 3 6 15 14 2.5
Electric
Heat
36 40 8 10.0
P Standard 380–415 50/60 3 3 7 15 14 2.5
Electric
Heat
32 40 8 10.0
Wire sizing listed in this table is based on Article 310, Table 310.16 of the NEC; at 104°F [40°C] ambient temperature. Follow your
local electrical codes. Use only copper conductors, rated for 194ºF [90°C] or higher, type THHN or better. No more than three cur-
rent carrying conductors per raceway. Contact your local Authority having jurisdiction if you have questions. Circuit breakers should
be UL 489 listed or better. Single phase circuit breakers for single phase machines only; three phase circuit breakers for all others.
Table 20
Specifications and Dimensions
F8410701ENR10
©