User Guide
Installation
801539
30
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
● If branch circuit to dryer is 15 feet (4.50 m) or
less in length, use U.L. (Underwriters
Laboratories) listed No. 10 A.W.G. wire (copper
wire only), or as required by local codes. If over
15 feet (4.50 m), use U.L. listed No. 8 A.W.G.
wire (copper wire only), or as required by local
codes. Allow sufficient slack in wiring so dryer
can be moved from its normal location when
necessary.
● The power cord (pigtail) connection between
wall receptacle and dryer terminal block IS NOT
supplied with dryer. Type of pigtail and gauge
of wire must conform to local codes and with
instructions mentioned on the following pages.
The method of wiring the dryer is optional and subject
to local code requirements. Refer to Figure 24.
Figure 24
D816I
1 3-Wire Grounded Neutral 120/240 Volt, 60 Hertz
AC 1 Phase Service Entrance Switch Box
(Refer to NOTE above)
4 Metallic or Non-Metallic Sheathed Cable
(Copper wire only)
5 Pigtail to Dryer (Refer to NOTE above)
2 30 Ampere Fuses or Circuit Breaker 6 Neutral
3 Neutral Wire 7 Terminal Block in Dryer
NOTE: The power cord (pigtail) is NOT supplied with the electric
dryer. Type of pigtail and gauge of wire must conform to local
codes and instructions.
The method of wiring the dryer is optional and subject to local
code requirements.
NOTE: Connect the dryer to the power supply with the
MAXIMUM RATED VOLTAGE listed on the nameplate.
1
2
3
4
5
6
7
POWER SUPPLY POWER SUPPLY
INTERMEDIATE
FUSE BOX (May
be omitted if
service entrance
box is fused)
WALL RECEPTACLE
PIGTAIL CONNECTION
L1 L2 L1 L2
DIRECT CONNECTION
INTERMEDIATE
SHUT-OFF BOX
(May or may
not be fused)
120 ± 12
V.A.C.
A Typical
30-Amp
Three-Wire
Receptacle
NEMA Type
10-30R
120 ± 12
V.A.C.
240 ± 12
V.A.C.
NOTE: Use COPPER WIRE only.
Shorter than 15 ft. (4.5 m) use 10 A.W.G.
Longer than 15 ft. (4.5 m) use 8 A.W.G.










