Specifications
150 Pound Capacity Models
Voltage Designation Specifications
Code Voltage Cycle Phase Wire
Full Load
Amps Breaker mm2
Q 200–240 50/60 3 3 17 20 2.5
N 440-480 50/60 3 3 11 16 2.5
P 380-415 50/60 3 3 11 16 2.5
NOTE: Follow your local electrical codes. Use only copper conductors, rated for 194°F [90ºC] or higher, type
THHN or better. No more than three current carrying conductors per raceway. Contact your local Authority
having jurisdiction if you have questions. Circuit breakers should be UL 489 listed or better. Single phase cir-
cuit breakers for single phase machines only; three phase circuit breakers for all others.
Table 28
Steam Requirements (Steam Heat Op-
tion Only)
WARNING
Hot Surfaces. Will cause severe burns. Turn steam
off and allow steam pipes, connections and compo-
nents to cool before touching.
W505
For machines equipped with optional steam heat, install piping in
accordance with approved commercial steam practices. Steam re-
quirements are shown in .Table 29 .
Steam Supply Information
Capacities 35 60 80 100 125/150
Steam inlet con-
nection, in. [mm]
1/2 [DN13] 1/2 [DN13] 1/2 [DN13] 1/2 [DN13] 3/4 [DN19]
Number of steam
inlets
1 1 1 1 1
Recommended
pressure, psi [bar]
30–80 [2.0–5.5] 30–80 [2.0–5.5] 30–80 [2.0–5.5] 30–80 [2.0–5.5] 30–80 [2.0–5.5]