Specifications

150 Pound Capacity Models
Voltage Designation Specifications
Code Voltage Cycle Phase Wire
Full Load
Amps Breaker AWG mm2
NOTE: Wire sizing listed in these tables is based on Article 310, Table 310.16 of the NEC; at 104°F [40°C] am-
bient temperature. Follow your local electrical codes. Use only copper conductors, rated for 194°F [90ºC] or
higher, type THHN or better. No more than three current carrying conductors per raceway. Contact your local
Authority having jurisdiction if you have questions. Circuit breakers should be UL 489 listed or better. Single
phase circuit breakers for single phase machines only; three phase circuit breakers for all others.
Table 22
CE Approval
35 Pound Capacity Models
Voltage Designation Specifications
Code Voltage Cycle Phase Wire
Full Load
Amps Breaker mm2
X 200–240 50/60 1/3 2/3 12/8 16/10 2.5
Q Standard 200–240 50/60 3 3 8 10 2.5
Electric
Heat
42 50 10
O** 208–240 60 3 3 17 20 4
N 440-480 50/60 3 3 23 25 2.5
P Standard 380-415 50/60 3 3 7 10 2.5
Electric
Heat
23 25 2.5
NOTE: Follow your local electrical codes. Use only copper conductors, rated for 194°F [90ºC] or higher, type
THHN or better. No more than three current carrying conductors per raceway. Contact your local Authority
having jurisdiction if you have questions. Circuit breakers should be UL 489 listed or better. Single phase cir-
cuit breakers for single phase machines only; three phase circuit breakers for all others.
**M30 Control Models Only.
Table 23
Specifications and Dimensions