Specifications

100 Pound Capacity Models
Voltage Designation Specifications
Code Voltage Cycle Phase Wire
Full
Load
Amps Breaker AWG mm2
Q (Through
4/13/10)
Standard 200–240 50/60 3 3 10 15 14 2.5
Electric
Heat
108 110 1 50
Q (Starting
4/14/10)
Standard 208–240 50/60 3 3 14 20 12 2.5
Electric
Heat
108 110 1 50
R (Through
7/6/10)
Standard 380–480 50/60 3 3 10 15 14 2.5
Electric
Heat
40 50 6 16
N (Starting
7/7/10)
Standard 440-480 50/60 3 3 10 15 14 2.5
Electric
Heat
40 50 6 16
P (Starting
7/7/10)
Standard 380-415 50/60 3 3 10 15 14 2.5
Electric
Heat
40 50 6 16
NOTE: Wire sizing listed in these tables is based on Article 310, Table 310.16 of the NEC; at 104°F [40°C] am-
bient temperature. Follow your local electrical codes. Use only copper conductors, rated for 194°F [90ºC] or
higher, type THHN or better. No more than three current carrying conductors per raceway. Contact your local
Authority having jurisdiction if you have questions. Circuit breakers should be UL 489 listed or better. Single
phase circuit breakers for single phase machines only; three phase circuit breakers for all others.
Table 20
Specifications and Dimensions
F8423301ENR3
©
Copyright, Alliance Laundry Systems LLC - DO NOT COPY or TRANSMIT 47