Specifications
Installation
Three-Wire Plug
NOTE: The power cord (pigtail) is NOT supplied with the electric
dryer. Type of pigtail and gauge of wire must conform to local
codes and instructions.
The method of wiring the dryer is optional and subject to local
code requirements.
NOTE: Connect the dryer to the power supply with the
MAXIMUM RATED VOLTAGE listed on the nameplate.
POWER SUPPLY
_1_
2
POWER SUPPLY
120-+12
V.A.C.
240 -+12
V.A.C,
A typical
30-Amp
Three-wire
Receptacle
NEMA Type
10-30R
_ 120-+12
, V.A.C.
INTERMEDIATE
FUSE BOX (May
be omitted if
service entrance
box is fused)
WALL RECEPTACLE
INTERMEDIATE
SHUT-OFF BOX
(May or may
r not be fused)
NOTE: Use COPPER WIRE only.
Shorter than 15 ft. (4.5 m) use 10 A.W.G.
Longer than 15 ft. (4.5 m) use 8 A.W.G.
L1 L2
PIGTAIL CONNECTION
L1 L2
DIRECT CONNECTION
2
3
3-Wire Grounded Neutral 120/240 Volt, 60 Hertz
AC 1 Phase Service Entrance Switch Box
(Refer to NOTE above)
30 Ampere Fuses or Circuit Breaker
Neutral Wire
4
5
6
7
Metallic or Non-Metallic Sheathed Cable
(Copper wire only)
Pigtail to Dryer (Refer to NOTE above)
Neutral
Terminal Block in Dryer
D8161
Figure 11
To Convert from 4-Wire Connection to 3-Wire
Connection
l. Disconnect power to dryer.
2. Remove access cover from rear of dryer.
Figure 12
D6951
512023 © Copyright, Alliance Laundry Systems LLC - DO NOT COPY or TRANSMIT 17










