Specifications

© Copyright, Alliance Laundry Systems LLC - DO NOT COPY or TRANSMIT
Specifications and Dimensions
35
C003292ENR1
Pocket Hardmount
Electrical Specifications
Voltage Designation Standard Electric Heat
Model
Code
Voltage
Cycle
Phase
Wire
Full Load
Amps
Breaker
AWG
mm
2
Full Load
Amps
Breaker
AWG
mm
2
40H
N 380 – 480 50/60 3 3 4 15 14 2.5 29 35 8 10
Q 200 – 240 50/60 3 3 8 15 14 2.5 56 60 6 16
X 200 – 240 50/60 1/3 2/3 11 15 14 2.5 56 60 6 16
60H
N 380 – 480 50/60 3 3 6 15 14 2.5 29 35 8 10
Q 200 – 240 50/60 3 3 11 15 14 2.5 84 90 3 25
X 200 – 240 50/60 1/3 2/3 12 15 14 2.5 84 90 3 25
80H
N 380 – 480 50/60 3 3 8 15 14 2.5 31 35 8 10
Q 200 – 240 50/60 3 3 15 20 12 4 87 110 2 35
100H
N 380 – 480 50/60 3 3 8 15 14 2.5 32 40 8 10
Q 200 – 240 50/60 3 3 15 20 12 4 88 110 2 35
125H
N 380 – 480 50/60 3 3 10 15 14 2.5
Not Available
Q 200 – 240 50/60 3 3 19 30 10 6
140H
N 380 – 480 50/60 3 3 11 15 14 2.5
Not Available
Q 200 – 240 50/60 3 3 20 30 10 6
175H
N 380 – 480 50/60 3 3 15 20 12 4 Not Available
40M
N 380 – 480 50/60 3 3 3 15 14 2.5 29 35 8 10
Q 200 – 240 50/60 3 3 5 15 14 2.5 56 60 6 16
X 200 – 240 50/60 1/3 2/3 9 15 14 2.5 56 60 6 16
60M
N 380 – 480 50/60 3 3 5 15 14 2.5 29 35 8 10
Q 200 – 240 50/60 3 3 9 15 14 2.5 84 90 3 25
X 200 – 240 50/60 1/3 2/3 11 15 14 2.5 84 90 3 25
80M
N 380 – 480 50/60 3 3 6 15 14 2.5 31 35 8 10
Q 200 – 240 50/60 3 3 11 15 14 2.5 87 110 2 35
100M
N 380 – 480 50/60 3 3 7 15 14 2.5 32 40 8 10
Q 200 – 240 50/60 3 3 12 15 14 2.5 88 110 2 35
140M
N 380 – 480 50/60 3 3 8 15 14 2.5
Not Available
Q 200 – 240 50/60 3 3 16 20 12 4
NOTE: Wire-size based on: NFPA 70 (NEC), Table 310.16, 75°C Column. No more than three current carrying
conductors per raceway. Use copper conductors only. Use circuit breakers only. Do not use fuses. Suggested breaker
size based on NFPA 70, Section 240.6. Contact local authority having jurisdiction for additional information. Local
electrical codes supersede all suggestions of this table. Follow all local electrical codes. Local is defined as place of
machine installation.
Table 15