Specifications

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Installation
F8429301ENR9
58
40 Pound Capacity Models
Voltage Designation Standard Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load
Amps
Circuit
Breaker
mm
2
Full Load
Amps
Circuit
Breaker
mm
2
F-Speed Models
N 440-480 50/60 3 3 3 15 2.5 22 30 6.0
X 220 – 240 50 1/3 2/3 7/4 10/6 2.5 N/A
Q 220 – 240 50 3 3 4 6 2.5 42 50 10.0
P 380 – 415 50 3 3 3 6 4.0 26 32 2.5
V-Speed Models
N 440-480 50/60 3 3 3 15 2.5 22 30 6.0
X 220 – 240 50 1/3 2/3 7/4 10/6 2.5 N/A
Q 220 – 240 50 3 3 4 6 2.5 42 50 10.0
P 380 – 415 50 3 3 3 6 2.5 26 32 2.5
NOTE: Wire sizes shown are for copper, THHN, 90°C conductor per NEC article 310.
Table 30
60 Pound Capacity Models
Voltage Designation Standard Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load
Amps
Circuit
Breaker
mm
2
Full Load
Amps
Circuit
Breaker
mm
2
F-Speed Models
N 440-480 50/60 3 3 4 15 2.5 22 30 6.0
X 220 – 240 50 1/3 2/3 11/7 16/10 2.5 N/A
Q 220 – 240 50 3 3 7 10 2.5 43 50 10.0
P 380 – 415 50 3 3 4 6 4.0 26 32 2.5
V-Speed Models
N 440-480 50/60 3 3 4 15 2.5 22 30 6.0
X 220 – 240 50 1/3 2/3 11/7 16/10 2.5 N/A
Q 220 – 240 50 3 3 7 10 2.5 43 50 10.0
P 380 – 415 50 3 3 4 6 2.5 26 32 2.5
NOTE: Wire sizes shown are for copper, THHN, 90°C conductor per NEC article 310.
Table 31