Electrical Specifications
Non-CE Models
20 Pound Capacity Models
Voltage Designation Standard Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load
Amps
Circuit
Breaker
AWG
mm
2
Full Load
Amps
Circuit
Breaker
AWG
mm
2
F-Speed Models
B 120 60 1 2 7 15 14 2.5 N/A
X 220 – 240 60 1/3 2/3 4/3 15 14 2.5 N/A
Q 220 – 240 60 3 3 3 15 14 2.5 21
30 10 6.0
N 440 – 480 60 3 3 2 15 14 2.5 N/A
P 380 – 415 50 3 3 2 15 14 2.5 13 15 14 2.5
V-Speed Models
B 120 60 1 2 8 15 14 2.5 N/A
X 220 – 240 60 1/3 2/3 4/3 15 14 2.5 N/A
Q 220 – 240 60 3 3 3 15 14 2.5 21 30 10 6.0
N 440 – 480 60 3 3 2 15 14 2.5 N/A
P 380 – 415 50 3 3 2 15 14 2.5 13 15 14 2.5
NOTE: Wire sizes shown are for copper, THHN, 90°C conductor per NEC article 310.
Table 21
30 Pound Capacity Models
Voltage Designation Standard Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load
Amps
Circuit
Breaker
AWG
mm
2
Full Load
Amps
Circuit
Breaker
AWG
mm
2
F-Speed Models
X 220 – 240 60 1/3 2/3 5/4 15 14 2.5 N/A
Q 220 – 240 60 3 3 4 15 14 2.5 22
30 10 6.0
N 440 – 480 60 3 3 3 15 14 2.5 N/A
P 380 – 415 50 3 3 3 15 14 2.5 13 15 14 2.5
V-Speed Models
X 220 – 240 60 1/3 2/3 6/4 15 14 2.5 N/A
Q 220 – 240 60 3 3 4 15 14 2.5 22 30 10 6.0
N 440 – 480 60 3 3 3 15 14 2.5 N/A
P 380 – 415 50 3 3 3 15 14 2.5 13 15 14 2.5
NOTE: Wire sizes shown are for copper, THHN, 90°C conductor per NEC article 310.
Table 22