Specifications
Adapter Specifications
Expansion I/O Capacity Maximum of 63 modules
Maximum of 5 Rack Optimized connections (for digital modules
only)
Maximum of 20 direct connections
1734-AENT backplane current output = 1.0A.
The actual number of modules can vary. Add up the current
requirements of the modules you want to use to make sure they do
not exceed the amperage limit of 1.0A for the 1734-AENT.
Backplane current can be extended beyond 1.0A by using
1734-EP24DC backplane extension Power Supplies. Add multiple
1734-EP24DC modules to reach the 63 module maximum).
Cat. No. PointBus Current Requirements
1734-IB2 75mA
1734-IB4 75mA
1734-IB8 75mA
1734-IV2 75mA
1734-IV4 75mA
1734-OB2 75mA
1734-OB4 75mA
1734-OB8 75mA
1734-OB2E 75mA
1734-OB2EP 75mA
1734-OB4E 75mA
1734-OB8E 75mA
1734-OV2E 75mA
1734-OV4E 75mA
1734-OW2 80mA
1734-OX2 100mA
1734-IE2C 75mA
1734-OE2C 75mA
1734-IE2V 75mA
1734-OE2V 75mA
1734-IA2 75mA
1734-IM2 75mA
1734-OA2 75mA
1734-IJ2 160mA
1734-IK2 160mA
1734-IR2 220mA
1734-IT2I 175mA
1734-SSI 110mA
1734-VHSC5 180mA
1734-VHSC24 180mA
1734-232ASC 75mA
1734-485ASC 75mA
EtherNet
Communication Rate
10/100Mbits/s, half or full-duplex