User manual

12 POINT I/O EtherNet/IP Adapter
Publication
1734-IN590B-EN-P - February 2005
Troubleshoot with the Indicators
Indication Probable Cause
System Power
Off Not active; field power is off or dc-dc converter problem
Green System power on; dc-dc converter active (5V)
Field Power
Off Not active; field power is off
Green Power on; 24V present
Module Status
Off No power applied to device
Flashing Red/Green LED powerup test (module self-test)
Green Device is operating normally
Flashing Red Recoverable fault has occurred:
Firmware (NVS) update
Network IP Address changed
CPU load exceeded
Solid Red Unrecoverable fault has occurred:
Self-test failure (checksum failure, or ramtest failure at
powerup)
Firmware fatal error
System Power
Field Power
43248aent
Module Status
Network Activity
Network Status
PointBus Status
Module
Status
Network
Activity
Network
Status
1734-AENT
PointBus
Status
Field
Power
System
Power
02