If the MOD status indicator is flashing red, take the following actions.
1. Cycle power to the drive.
2. If cycling power does not correct the problem, the adapter parameter
settings
may have been corrupted. Reset defaults and reconfigure the
adapter.
3. If resetting defaults does not correct
the problem, flash the adapter with
the latest firmware release.
If the MOD status indicator is solid red, tak
e the following actions.
1. Cycle power to the drive.
2. Replace the adapter.
If the MOD status indicator is flashing green, tak
e the following
actions.
1. Place the scanner in R
UN mode.
2. Program the controller to recognize and transmit I/O to the adapter.
3. Configure the adapter for the prog
ram in the controller.
4. Normal behavior if no DPI I/O is enabled.
If the NET A status indicator is
off, take the following actions.
1. Securely connect the adapter to the drive using the Internal Interface
(
ribbon) cable and to the network using an Ethernet cable.
2. Correctly connect the Ethernet cable
to the Ethernet connector.
3. Set a unique IP
address using a BOOTP server or by disabling BOOTP
and using adapter parameters.
4. Apply power to the drive (or adapter, if mounted in a DPI External
Co
mms kit) and network.
If the NET A status indicator
is flashing red, take the following actions.
1. Place the scanner in R
UN mode.
2. Check the amount of traffic on the network.
If th
e NET A status indicator is flashing green, take the following actions.
1. Place the controller in RU
N mode.