If the PORT status indicator is off, take the following actions.
1. Securely connect the adapter to the drive using the Internal Interface
(ribb
on) cable.
2. Apply power to the drive.
If t
he PORT status indicator is flashing
red, take the following actions.
1. Verify the setting for Parameter 22 - [DSI I/O Cfg].
2. Verify that cables are securely connected and not damaged; replace
cables if
necessary.
3. Cycle power to the drive.
4. Use Allen-Bradley P
owerFlex 4/40 drives.
If the MOD status indicator is of
f, take the following actions.
1. Securely connect the adapter to the drive using the Internal Interface
(ribb
on) cable.
2. Apply power to the drive.
NET A Off One of the following:
• The adapter and/or network is
not powered.
• The adapter is
not properly connected to the network.
• The adapter needs an IP address.
Follow the correc
tive action below.
Solid Red The adapter failed the duplicate IP address detection test. Configure the
adapter to use a unique IP address and cy
cle power.
Flashing Red An EtherNet/IP connection has timed out. Follow the corrective action below.
Flashing Green The adapter is properly connected but is not communicating with any devices
on the network.
Solid Green The adapter is properly connected and communicating on the network. No
action is required.
NET B Off If the adapter is idle, normal condition. No action is required.
If the adapter is not idle, then the adapter is not powered or
is not transmitting
on the network. In this case, follow the corrective action below.
Flashing Green The adapter is transmitting on the network. No action is required.
Module Status Indicator
Indic
ator Status Description