Status Indicators Appendix A
If the MS indicator is off, take the following actions.
1. Check the host power supply.
2. Verify that the daughtercard is fir
mly seated in the host’s slot.
3. Replace daughtercard or host.
If the MS indic
ator is red and the host is holding the
daughtercard in reset or the host is faulted, take the following
actions.
1. Verify that the daughtercard is fir
mly seated in the host’s slot.
2. Clear the host’s fault.
3. Replace daughtercard or host.
If the MS indicator is r
ed and an unrecoverable fault has
occurred, take the following actions.
1. Cycle power to the host.
2. Replace the daughtercard or host.
If the NS status indicator is flashing green,
take the following actions.
1. If no connections are configured, this is nor
mal operation.
No action is required.
2. If connections are configure
d, check connection originator for
connection error code.
If the LNK status indicator is off, ta
ke the following actions.
1. Verify that all Ethernet c
ables are connected.
2. Verify that the Ethernet switch is powered.