User manual
186 Publication ENET-UM001I-EN-P - January 2010
Appendix A Status Indicators
If the OK status indicator is off, take the following actions.
1. Verify there is power.
2. Verify that the module is properly installed.
Link Status Indicator
Indicator
Conditi
on
Status Description
Off Link lost No data is being transmitted. Check to see if any cables are disconnected.
Green XXX.XXX.XXX.XXX OK The module is ready to communicate. No action is required.
Flashing
green
Data is being transmitted. The module is communicating over the network. No
action is required.
OK Status Indicator
Indicator
Cond
ition
Status Description
Off The module does not have 5V DC power.
Follow the corrective action below.
Flashing
Green
BOOTP - XX:XX:XX:XX:XX:XX or
xx:xx:xx:xx:x
x:xx
DHCP - XX:XX:XX:XX:XX:XX
The module is not configured. Configure the module
Green XXX.XXX.XXX.XXX OK The module is operating correctly. No action is required.
Flashing red
Duplicate IP XX:XX:XX:XX:XX:XX
A device with the Ethernet MAC address of xx:xx
:xx:xx:xx:xx is using the IP
address of this module.
Make sure that the the IP address assigned to this module is not identical to
that of any other device already on
the network.
Flash Update A firmware update is in progress. No action is required.
Flashing Red
and Green
Rev %d.%d.%d The module is performing a self test while it is being started. No action is
required.