User manual

172 Publication ENET-UM001I-EN-P - January 2010
Appendix A Status Indicators
If the OK status indicator is off, take the following actions.
1. Verify that there is chassis power.
2. Verify that the module is completely inser
ted into the chassis and
backplane.
If the OK status indicator is r
ed, take the following actions.
1. Cycle power to the module.
2. If this does not clear the fault, replace the module.
Link Status Indicator
Indicator
condi
tion
Status Description
Off Link lost No data is being transmitted. Check to see if any cables are disconnected.
Green XXX.XXX.XXX.XXX OK The module is ready to communicate. No action is required.
Flashing
green
Data transmission in progress. No action is required.
OK Status Indicator
Indicator
condit
ion
Status Description
Off The module does not have 24V DC power.
Follow the corrective action below.
Flashing
green
BOOTP - XX:XX:XX:XX:XX:XX or
xx:xx:xx:x
x:xx:xx
DHCP - XX:XX:XX:XX:XX:XX
The module is not configured. Configure the module.
Green XXX.XXX.XXX.XXX OK The module is operating correctly. No action is required.
Flashing
red
Duplicate IP XX:XX:XX:XX:XX:XX
A device with the Ethernet MAC address of xx:xx:xx
:xx:xx:
xx is using the IP address of
this module.
Make sure that the the IP address assigned to this
module is not identical to that of any
other device already on the network.
Flash Update A firmware update is in progress. No action is required.
Red Severe Fault An unrecoverable fault has been detected.
Follow the corrective action below.
Flashing
red/green
Rev %d.%d.%d The module is performing a self test while it is being started. No action is required.