User manual

118 Publication ENET-UM001I-EN-P - January 2010
Chapter 7 Interlocking and Data Transfer Between Controllers
Receive MSGs from PLC-5 or SLC 500 Processors
To receive MSGs from PLC-5 or SLC 500 processors,
1. If the originating controller
is a PLC-5 or SLC 500 processor, in the
MSG instruction, select PLC5.
2. On the MultiHop tab, specify:
the IP address of the EtherNet/IP
communication module that is
local to the Logix5000 controller.
the slot number of the Logix5000 controller.
If the controller
is a
For this section And this item Specify
PLC-5 This PLC-5 Communication Command
PLC-5 Typed Read or PLC-5 Typed Write
Data Table Address Starting address of the data in the PLC-5 controller
Size in Elements Number of elements to read or write
Port Number 2
Target Device Data Table Address Type, in quotation marks [“ “], the name of the tag in the
Con
t
rolLogix controller (for example, “count”).
MultiHop
Select
Yes.
SLC 500 This Controller Communication Command
PLC5 Read or PLC5 Write
Data Table Address Starting address of the data in the SLC 500 controller
Size in Elements Number of elements to read or write
Channel 1
Target Device Data Table Address Type, in quotation marks [“ “], the name of the tag in the
Con
t
rolLogix controller (for example, “count”).
MultiHop
Select
Yes