Chapter 7 Interlocking and Data Transfer Between Controllers
For a message to a SLC 500 or PLC-5 processor, this RSLogix Message
Configuration dialog box appears.
5. If the targ
et module is
configured in the I/O Configuration folder of
the originating controller, click Browse to select the module or manually
enter the path to the target module.
A manually entered path begins with the name of the local EtherNet/IP
module, the por
t the message exits (2 for EtherNet/IP), and the IP
address of the next module in the path, which could be the target
module.
Communication path from a Logix5000 controller to a Logix5000 controller over
an EtherNet/IP network
washer, 2, 127.127.127.12, 1, 0
Ethernet Network
5
5
5
0
E
N
B
T
5
5
5
0
E
N
B
T
IP Address
127.127.127.12
Message
Where Indicates
Washer Name of the 1756-ENBT, 1756-EN2T, or 1756-EN2F module
2 Ethernet port of the 1756-ENBT, 1756-EN2T, or EN2F module
127.127.127.
12
IP address of the 1756-ENBT, 1756-EN2T, or 1756-EN2F module in
the destination chassis
1 Backplane port of the 1756-ENBT, 1756-EN2T, or 1756-EN2F
module in the destination chassis
0 Slot number of the destination controller