112 Publication ENET-UM001I-EN-P - January 2010
Chapter 7 Interlocking and Data Transfer Between Controllers
Configure a MSG to an SLC 500 Processor
If the data is And you want to For this item Type or select
Integer Read (receive) data Message Type SLC Typed Read
Source Element Data table address in the SLC 500 controller (for example, N7:10)
Number of Elements Number of integers to transfer
Destination Tag First element of int_buffer
Write (send) data Message Type SLC Typed Write
Source Tag First Element of int_buffer
Number of Elements Number of integers to transfer
Destination Element Data table address in the SLC 500 controller (for example, N7:10)
Floating-point (REAL) Read (receive) data Message Type SLC Typed Read
Source Element Data table address in the SLC 500 controller (for example, F8:0)
Number of Elements Number of values to transfer
Destination Tag First element of the tag (controller-scoped) in this controller for
the data
Write (send) data Message Type SLC Typed Write
Source Tag First element of the tag (controller-scoped) in this controller that
c
ontains the data
Number of Elements Number of values to transfer
Destination Element Data table address in the SLC 500 controller (for example, F8:0)