Chapter 7 Interlocking and Data Transfer Between Controllers
5. Configure your new module.
a. In the Name field, type the name of your module.
b. From the Comm Format pull-down menu, select a communication
format.
c
. In the Slot field, type the chassis slot number.
d. In the Chassis Size field, type the chassis size.
e. From the Revision pull-down menu, select a revision number.
f. In the IP Address field, type the module IP address.
g. From the Electronic Keying pull-do
w
n menu, select Compatible
Module.
6. Click OK.
Enter a Message
To enter a message, perform this procedure.
1. Use relay ladder logic to enter a MSG instruction.
2. Click the button to configure the MSG instr
uction.
...
EXAMPLE
Enter a MSG instruction
If count_send = 1 and count_msg.EN = 0 (MSG instruction is not already enabled), then execute a MSG instruction that sends data to
another controller.
count_send
/
count_msg.en
EN
DN
ER
Type - Unconfigured
Message Control count_msg
...
MSG