User manual

108 Publication ENET-UM001I-EN-P - January 2010
Chapter 7 Interlocking and Data Transfer Between Controllers
3. Add the remote controller.
Select a communication format for a communication module based on the
modules in its remote c
hassis.
To add a module to the I/O Configuration folder, perform this procedure.
1. In RSLogix 5000 programming software, right-click the level to which
y
ou want to add the new module and choose New Module.
Module Communication Formats
If Select a communication format that specifies
The remote chassis contains only analog modules, diagnostic digital modules,
fused output modules, or communication modules
None
The
remote chassis only contains standard, digital input and output modules
(no diagnostic modules or fused output module
s)
Rack Optimization
You want to receive I/O module and chassis slot information from a
rack-optimize
d remote chassis owned by another controller
Listen-Only Rack Optimization