User manual

Publication 1734-UM011A-EN-P - February 2004
Configure the 1734-AENT for Direct Connection and Rack Optimization in RSLogix 5000 5-11
Add the POINT I/O Module and Configure For Rack Optimization
1. Highlight the 1734-AENT under I/O Configuration, right click and
select New Module.
The Select Module Type window will open.
2. Choose the 1734-OV4E/C module.
3. Click OK.
The Module Properties window will open.
4. Enter a Name, Slot, Comm Format, and Comm Format.
The Comm Format is Rack Optimization because we are configuring a
mixed direct connection and rack optimized connection, with the
1734-OVE4/C digital output module configured for a rack optimized
connection.