Publication 1734-UM011A-EN-P - February 2004
1-4 About the 1734-AENT Adapter
Power Up a System For the First Time
When POINT I/O is powered for the first time, the adapter must assign
addresses to every module in the backplane. POINT I/O modules all ship
configured at the same address. Therefore, at first power up, it is expected that
all but one module on the backplane will exhibit a solid red Module Status
LED. One by one the adapter will reset these modules and address them
appropriately. The amount of time that this operation takes is proportional to
the size of your POINT I/O system.
Adapter Features
The 1734-AENT adapter’s features include:
use of EtherNet/IP messages encapsulated within standard
TCP/UDP/IP protocol
common application layer with ControlNet and DeviceNet
interfacing via Category 5 rated twisted pair cable
half/full duplex 10 Mbit or 100 Mbit operation
DIN rail mounting
communication to and from other POINT I/O modules on the same
DIN rail
communication supported by RSLinx software
IP address assigned via standard BootP or DHCP tools
I/O configuration via RSLogix 5000 software
no network scheduling required
no routing tables required
supports connections from multiple controllers simultaneously