1734-POINT I/O Module/RSLogix 5000 Controller Tag Reference C-35
SSI Word Delay Time Note:
To enter Delay values from +32,768 to +65,535 µs, use this conversion
formula:
Desired Delay Value (in µs) - 65536 = Entered Delay Value (in µs).
Example: For a 40ms delay time, 40000 - 65536 = -25536
Sensor Resolution Note:
To enter Resolution values from +32,768 to +65,535 µ s, use this conversion
formula:
Desired Resolution Value - 65536 = Entered Resolution Value.
Example: For a 40,000 count sensor, 40000 - 65536 = -25536
Sensor Cycle Note:
To enter Cycle values from +32,768 to +65,535, use this conversion formula:
Desired Cycle Value - 65536 = Entered Cycle Value.
Example: For 50,000 sensor cycle rotations, 50000 - 65536 = -15536
Compare 0,1 Value Note:
To enter Compare values from +2,147,483,647 to +4,294,967,295, use this
conversion formula:
Desired Compare Value - 4,294,967,296 = Entered Compare Value.
Example: For a 3,000,000,000 compare value,
3,000,000,000 - 4,294,967,296 = -1,294,967,296