98 Publication 1756-RM093F-EN-P - January 2010
Appendix D Checklists for GuardLogix Safety Applications
Checklist for Safety Outputs
For programming or start up, an individual requirement checklist must
be filled in for every single SIL output channel in a system. This is the
only way to make sure that the requirements are fully and clearly
implemented. This checklist can also be used as documentation on
the connection of external wiring to the application program.
Output Checklist for GuardLogix System
Company
Site
Safety Function Definition
SIL Output Channels
Number Output Module Requirements
Fulfilled
Comment
Yes No
1 Have you followed installation instructions and precautions to conform to applicable
safety standards?
2 Have you performed functional verification tests on the modules?
3 Have you uploaded and compared the configuration of each module to the
configuration sent by configuration tool?
4 Have you verified that test outputs are not used as safety outputs?
5
Are modules wired in compliance with PLe/Cat. 4 according to ISO 13849-1?
(1)
6 Have you verified that the electrical specifications of the output and the actuator are
compatible?
(1) For information on wiring your CIP Safety I/O module, refer to the product documentation for your specific module.