User manual

Publication 1756-RM093F-EN-P - January 2010 55
Safety Application Development Chapter 6
Specification of the Control Function
You must create a specification for your control function. Use this
specification to verify that program logic correctly and fully addresses
your application’s functional and safety control requirements. The
specification may be presented in a variety of formats, depending on
your application. However, the specification must be a detailed
description that includes (if applicable):
sequence of operations.
flow and timing diagrams.
sequence charts.
program description.
program print out.
written descriptions of the steps with step conditions and
actuators to be controlled. This includes:
input definitions.
output definitions.
I/O wiring diagrams and references.
theory of operation.
matrix or table of stepped conditions and the actuators to be
controlled, including the sequence and timing diagrams.
definition of marginal conditions, for example, operating modes
and EMERGENCY STOP.
The I/O portion of the specification must contain the analysis of field
circuits, that is, the type of sensors and actuators.
Sensors (Digital or Analog)
Signal in standard operation (dormant current principle for
digital sensors, sensors OFF means no signal)
Determination of redundancies required for SIL levels
Discrepancy monitoring and visualization, including your
diagnostic logic
Actuators
Position and activation in standard operation (normally OFF)
Safe reaction/positioning when switching OFF or power
failure
Discrepancy monitoring and visualization, including your
diagnostic logic