Characteristics of Safety Tags, the Safety Task, and Safety Programs Chapter 5
SIL 2 Outputs
Follow these guidelines for SIL 2 outputs:
Guard I/O output modules used for SIL 2 safety outputs must be
configured for dual-channel operation.
All Guard I/O output modules are approved for use in SIL 2
applications.
1732DS-IB8XOBV4
1791DS-IB8XOBV4, 1791ES-IB8XOBV4
1791DS-IB4XOW4
1791DS-IB8XOB8
1734-OB8S
SIL3 Safety – the Safety
Task
Creation of a GuardLogix project automatically creates a single safety
task. The safety task has these additional characteristics:
GuardLogix controllers are the only controllers that support the
safety task.
The safety task cannot be deleted.
GuardLogix controllers support a single safety task.
Within the safety task, you can schedule multiple safety
programs composed of multiple safety routines.
You cannot schedule or execute standard routines from within
the safety task.
The safety task is a periodic timed task with a user-selectable task
priority and watchdog. In most cases, it is the controller’s top priority
and the user-defined program watchdog must be set to accommodate
fluctuations in the execution of the safety task.
IMPORTANT
You cannot use Flex or 1756 output modules in EN 50156
SIL 2 applications.