User manual

26 Publication 1756-RM093F-EN-P - January 2010
Chapter 2 GuardLogix Controller System
Communication Bridges
These communication interface modules are available to facilitate
communication over Ethernet/IP, DeviceNet, and ControlNet networks
via the CIP Safety protocol.
EtherNet/IP Network
Peer-to-peer safety communication between GuardLogix controllers is
possible via the EtherNet/IP network through the use of 1756-ENBT,
1756-EN2T, or 1768-ENBT bridge modules. An EtherNet/IP bridge
module lets the GuardLogix controller control and exchange safety
data with CIP Safety I/O modules on an EtherNet/IP network.
Peer-to-peer Communication via 1756-ENBT Modules and the EtherNet/IP Network
GuardLogix System Communication Modules
1756 1756-ENBT, 1756-EN2T, or 1756-EN2F EtherNet/IP bridge
module
1734-AENT POINT I/O Ethernet Adapter
1756-DNB DeviceNet bridge module
1756-CN2 ControlNet bridge module
1756-CN2R Redundant ControlNet bridge module
1768 1768-ENBT
1734-AENT POINT I/O Ethernet Adapter
1768-CNB
1768-CNBR
IMPORTANT
Due to the design of the CIP Safety control system, CIP safety
bridge devices, like those listed in the table, are not required to
be SIL 3-certified.
1768-PB3
1768-L43S
1768-ENBT
1769-ECR
1756-L62S
1756-LSP
1756-DNB
1756-ENBT
Controller A
Controller B
Ethernet Switch
CIP Safety I/O Module
CIP Safety I/O Module
DeviceNet Network
EtherNet/IP
Network
EtherNet/IP
Network
CIP Safety I/O Module
CIP Safety I/O Module