User Guide

Publication DNET-UM004A-EN-P - March 2004
Configure Your Network Online 6-9
Configure the Scanner
To configure the scanner to communicate with the devices on your
network, you set up a scan list in the scanner. Then you define
memory locations for the data of each device.
To configure the scanner online:
Scanner
Scan List
device at address 1
device at address 2
device at address 3
scan list – A list in the scanner that identifies the devices with which the
scanner communicates. For each device in its scan list, the scanner sets aside
input and/or output memory for the data of the device.
Output Memory
DINT Input Memory
0
device at address 1
1
2
device at address 2
3
4
device at address 3
5
Step: See page:
Upload the Current Configuration of the Scanner 6-10
Define the Properties of the Scanner 6-11
Set the Alignment Option 6-12
Clear or Set the Automap on Add Check Box 6-13
Build the Scan List 6-14
Manually Assign Each Device to a Memory Location 6-15
Download the Configuration to the Scanner 6-16