User Guide
Publication DNET-UM004A-EN-P - March 2004
5-4 Connect Each Device to the Network
Procedures for Specific
Devices
The following sections show how to set the address of specific
devices.
ControlLogix Scanner 1756-DNB
CompactLogix Scanner 1769-SDN
For this device: See page:
ControlLogix Scanner 1756-DNB 5-4
CompactLogix Scanner 1769-SDN 5-4
ControlNet to DeviceNet Linking Device 1788-CN2DN 5-5
DriveLogix and FlexLogix Scanner 1788-DNBO 5-5
EtherNet/IP to DeviceNet Linking Device 1788-EN2DN 5-6
SoftLogix5800 Scanner 1784-PCIDS 5-10
DeviceNet
TM
MOD/NET I/O OK
1. Connect the device to the network. (If disconnected or the network power is off, the
pushbutton changes the baud rate.)
2. Turn on the power to the device.
3. Press and hold the manual configuration pushbutton until the device displays the desired
address.
When you release the button, the device resets to the new address.
4. After the device resets, check the 4-character display on the front of the module:
If: Then the:
A#address address is OK
Duplicate Node Address address conflicts with another device
The 1769-SDN device has no hardware mechanism to set its address.
1. Connect the device to the network.
2. Turn on the power to the device.
3. Use RSNetWorx software to set the address of the device. See Set an Address with
Software on page 5-3.
4. After the device resets, check the 2-character display on the front of the device. It shows
the status code and address of the device (status code first, then address).