User manual

Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 87
Communication Networks Chapter 5
A common application layer with ControlNet and DeviceNet networks
Network connections via an RJ45 cable
Support half/full duplex 10 MB or 100 MB operation
Support standard switches
ControlLogix EtherNet/IP Communication Modules
For EtherNet/IP network communication in a ControlLogix system, you have
several modules to choose from. Ta b l e 1 3
lists modules and their primary
features.
Table 13 - EtherNet/IP Communication Modules and Capabilities
Module Is used to
1756-ENBT Connect controllers to I/O modules (requires an adapter for distributed I/O).
Communicate with other EtherNet/IP devices (messages).
Serve as a pathway to share data between Logix5000 controllers (produce/consume).
Bridge EtherNet/IP nodes to route messages to devices on other networks.
1756-EN2T Perform the same functions as a 1756-ENBT module, with twice the capacity for more
demanding applications.
Provide a temporary configuration connection via the USB port.
Configure IP addresses quickly by using rotary switches.
1756-EN2F Perform the same functions as a 1756-EN2T module.
Connect fiber media by an LC fiber connector on the module.
1756-EN2TR Perform the same functions as a 1756-EN2T module.
Support communication on a ring topology for a Device Level Ring (DLR) single-fault
tolerant ring network.
1756-EN2TRXT Perform the same functions as a 1756-EN2T module.
Support communication on a ring topology for a Device Level Ring (DLR) single-fault
tolerant ring network.
Operate in extreme environments with -25…70 °C (-13…158 °F) temperatures.
1756-EN3TR Perform the same functions as the 1756-EN2TR module.
Extended Integrated Motion on EtherNet/IP network.
Support of up to 128 motion axes.
1756-EN2TSC Perform the same functions as a 1756-ENBT module, with twice the capacity for more
demanding applications.
Provide a temporary configuration connection via the USB port.
Configure IP addresses quickly by using rotary switches.
1756-EN2TXT Perform the same functions as a 1756-EN2T module.
Operate in extreme environments with -25…70 °C (-13…158 °F) temperatures.
1756-EWEB Provide customizable web pages for external access to controller information.
Provide remote access via an internet browser to tags in a local ControlLogix controller.
Communicate with other EtherNet/IP devices (messages).
Bridge EtherNet/IP nodes to route messages to devices on other networks.
Support Ethernet devices that are not EtherNet/IP-based with a socket interface.
This module does not provide support for I/O or produced/consumed tags.