User manual
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014 135
I/O Modules Chapter 8
8. Specify the Module Properties according to your module and application.
For more information about the module configuration properties, see the
user manual for the I/O module you are adding.
9. Add any other I/O modules that you are using in this bus.
10. Complete steps 1
…9 until your remote I/O network and distributed I/O
modules are configured.
Reconfigure an I/O Module
If an I/O module supports reconfiguration, you can reconfigure the module via
the following:
• The Module Properties dialog box in the I/O Configuration folder
• A MSG instruction in program logic
Use a MSG instruction of type Module Reconfigure to send new configuration
information to an I/O module. During the reconfiguration, consider the
following:
• Input modules continue to send input data to the controller
• Output modules continue to control their output devices
Reconfigure an I/O Module Via the Module Properties
To reconfigure an I/O module by using the module properties, right-click the
module in the I/O Configuration tree and choose Properties. Then, edit the
properties that you must change and click Apply.
IMPORTANT
Use care when changing the configuration of an I/O module. You can
inadvertently cause the I/O module to operate incorrectly.