Specifications
Allen-Bradley ControlLogix Ethernet Driver Help
Possible Cause:
A tag address that has been specified statically contains an array reference for an address type that doesn't
support arrays.
Solution:
1. Re-enter the address in the client application to remove the array reference.
2. Correct the address type.
Data type <type> is not valid for device address <address>.
Error Type:
Warning
Possible Cause:
A tag address that has been specified statically has been assigned an invalid data type.
Solution:
Modify the requested data type in the client application.
Device address <address> contains a syntax error.
Error Type:
Warning
Possible Cause:
A tag address that has been specified statically contains one or more of the following errors.
1. Address doesn’t conform to the tag address naming conventions.
2. Address is invalid according to the address format and underlying Controller tag data type.
3. A Program tag was specified incorrectly.
4. An invalid address format was used.
Solution:
Re-enter the address in the client application.
See Also:
Addressing Atomic Data Types
Address Formats
Device address <address> is not supported by model <model name>.
Error Type:
Warning
Possible Cause:
A tag address that has been specified statically references a location that is valid for the communications protocol
but not supported by the target device.
Solution:
Verify the address is correct; if it is not, re-enter it in the client application. Also verify that the selected model
name for the device is correct.
Device address <address> is read only.
Error Type:
Warning