Specifications
Allen-Bradley ControlLogix Ethernet Driver Help
Logix Options
Descriptions of the parameters are as follows:
l Protocol Mode: This parameter specifies how Logix tag data is read from the controller. This option
should only be changed by advanced users who are looking to increase client/server tag update
performance. Options include Symbolic Mode, Logical Non-Blocking Mode and Logical Blocking Mode. The
server project is interchangeable between these three modes. The default setting is Logical Non-Blocking
Mode. For more information, refer to Choosing a Protocol Mode.
Note: Logical Non-Blocking Mode and Logical Blocking Mode are not available to Serial Gateway models.
l Online Edits: When enabled, the driver synchronizes its own project image with that of the controller
project when an online project edit (or project download from RSLogix/Studio5000) is detected. This
option prevents unnecessary errors from occurring during a project change. It is only available when the
selected protocol is Logical Mode. The default setting is Yes.
l Offline Edits: When enabled, the driver synchronizes its own project image with that of the controller
project when an offline project edit (or project download from RSLogix/Studio5000) is detected. This
option prevents unnecessary errors from occurring during a project change. It is only available when the
selected protocol is Logical Mode. The default setting is Yes.
Caution: Failure to synchronize with project changes can lead to reading from and writing to the wrong
Native tag address.
l Automatically Read String Length: When checked, the driver automatically reads the LEN member of
the STRING structure whenever the DATA member is read. The DATA string is terminated at the first null
character encountered, the character whose position equals the value of LEN, or the maximum string
length of DATA (whichever occurs first). When unchecked, the driver bypasses the LEN member read
and terminates the DATA string at either the first null character encountered or the maximum string
length of DATA (whichever occurs first). Therefore, if LEN is reduced by an external source without
modification to DATA, the driver does not terminate DATA according to this reduced length. The default
setting is Yes.
l Default Type: This parameter specifies the data type assigned to a client/server tag when the default
type is selected during tag addition, modification, or import. The default setting is Default. For more
information, refer to Default Data Type Conditions.
Note 1:If Default is selected, the driver retrieves the Logix tag's data type from the controller when a
www. kepware.com