User manual
28 Rockwell Automation Publication 1609-UM009C-EN-P - February 2015
Bulletin 1609 UPS
Technical Specifications —1609-D, 230V 1609-D600E 1609-D1000E 1609-D1500E
Input V nom. 230V
Capacity 600 VA (390W) 1000 VA (650W) 1500 VA (980 W)
Voltage Range, default 180...280V
Voltage Range, widest online 180...280V
Current nom. 3.3 A 4.7 A 7.1 A
Capacity Frequency 50/60 Hz ±3Hz
PFC None (load power factor is reflected in the input line current)
Output V nom. 230V
Capacity 600 VA (390 W) 1000 VA (650 W) 1500 VA (980 W)
Online Output Voltage Range, default 207...253V
Output Voltage Range, widest online 207...253V
Transfer Point Accuracy ±3%
On Battery V nom 230V (Sine Wave)
Frequency 50/60 Hz ±0.5 Hz (Factory default: 50 Hz ± 0.5 Hz)
THD ≤ 10% (Full Linear Load)
Short Circuit Protection Crest Factor 2.2:1
Efficiency On Battery (Typical with resistive load) 75%(Typical with resistive load)
Online - Typical with resistive load excluding AVR mode) 86% 94% 95%
Protection Surge 660 Joules (Total performance rated with 10 x 1000 μs Pulse)
Overload (Shutdown after 10 s) > 110...130%
Overload (Shutdown immediately) > 130%
Output Short Online/Battery Premises branch circuit over-current protection/Shutdown
Thermal Protection UPS inside temperature ≥ 60 ºC
Regulatory Safety UL1778, CSA C22.2 No. 107.3-5, EN/IEC62040-1
EMC FCC & CE (Class A)
Markings UL, cULus, FCC, CE
Battery Pack Run Time ≥5 min (at 25 °C, full R load) ≥3.5 min (25 °C, full R load) ≥2.5 min (at 25 °C, full R load)
Type Sealed Lead Acid Battery 12V/5Ah (for 0...40 °C B.B. BP5-12) 12V/5.5Ah (for 0...50 °CB.B. HRL5.5-12)
Voltage 36V
Charger Current limited, constant voltage float charger
Recharger Time Less than 8 hr to 90% capacity after discharge with full load
Lifetime 2...3 years at 25 °C ambient temperature
Environment Temperature Operating Standard Battery 0...+40 °C (+32...+104 °F) Hi-Temperature Battery 0...+50 °C (+32...+122 °F)
Non-operating/Storage -15...+45 °C (+5...+113 °F)
Altitude Operating 0...6600 feet (0... 2000 meters)
Humidity Operating/Storage 5...95% RH (Non-condensing)
Heat Output On Line, Full load: 217 BTU/hr
On Line, Full load, Charging:
296 BTU per hour
On Battery: Full Load: 1331 BTU
per hour
On Line, Full load: 142BTU/hr
On Line, Full load, Charging:
221 BTU per hour
On Battery: Full Load: 2218BTU
per hour
On Line, Full load: 176BTU/hr
On Line, Full load, Charging:
256BTU per hour
On Battery: Full Load: 3344BTU
per hour
Audible Noise < 50 dBA @ Front Side 1 Meter
Mechanical Approximate Dimensions L*W*H In. (mm) 16.15 x 8.67 x 10.24 (410 x 220 x 260 )
Approximate Weight lbs (kg) 29.7 (13.5) 30.1 (13.7 ) 31 lb (14.1)