Datasheet

Rockwell Automation 10-57
Serie 194C, 194L
Control and Load Switches
10
Specifications
IEC Performance Data for 194C, 194L
194C 194L
10 A 12 A 16 A 20 A 25 A
Rated Power
P
e
Rated voltage [V] Contacts in series
24 1 [kW] 0.12 0.15 0.20 0.25
DC-23A, DC-3, DC-5 24 2 [kW] 0.20 0.25 0.30 0.37
For inductive loads T 7.5 ms 48 2 [kW] 0.25 0.30 0.37 0.50
48 3 [kW] 0.30 0.37 0.50 0.75
60 2 [kW] 0.25 0.30 0.37 0.50
60 4 [kW] 0.37 0.50 0.75 1.00
110 4 [kW] 0.50 0.75 1.00 1.20
110 6 [kW] 1.00 1.20 1.40 1.60
220 4 [kW] 0.37 0.50 0.75 1.00
220 6 [kW] 1.00 1.20 1.40 1.50
Rated Making/Breaking Capacity
(=4 x I
e
)
1.05 x rated voltage [V] Contacts in series
25.2 1 [A] 20.0 25.0 33.3 41.6
DC-23A, DC-3, DC-5 25.2 2 [A] 33.3 41.6 50.0 61.6
For inductive loads T 15 ms 50.4 2 [A] 21.0 25.0 30.8 41.6
50.4 3 [A] 25.0 30.8 42.0 62.4
63 2 [A] 16.6 20.0 24.6 33.2
63 4 [A] 24.6 33.3 50.0 66.4
115.5 4 [A] 18.1 27.2 36.4 44.0
115.5 6 [A] 36.4 43.6 51.0 58.2
231 4 [A] 6.7 9.1 13.6 18.2
231 6 [A] 18.1 21.8 25.2 27.2
Rated Breaking Capacity at 220 V [A] 60 72 96 128 176
[cos ϕ] 0.65 0.65 0.65 0.65 0.35
at 400 V [A] 55 72 96 128 176
[cos ϕ] 0.65 0.65 0.65 0.65 0.35
at 690 V [A] 53 72 86 112
[cos ϕ] — 0.65 0.65 0.65 0.35
Rated Power
P
e
IEC 947 240 V [kW]
2.5 3 4 5.5 5.5
AC-2 Slip-ring motors: starting, reversing, 3-phase / 380 V [kW] 4.5 5.5 7.5 9 13
and regenerative braking 3-poles 415 V [kW] 4.5 5.5 7.5 9 13
Star-Delta starting 440 V [kW] 4.5 5.5 7.5 9 13
500 V [kW] 5.5 7.5 10 11 15
690 V [kW] 7.5 10 11 15
AC-3 Squirrel-cage motors: starting IEC 947 220…240 V [kW] 1.5 2.2 3 4.5 5.5
and stopping of running motors 3-phase / 380…440 V [kW] 2.2 4 5.5 7.5 11
3 poles 500 V [kW] 5.5 7.5 10 13
690 V [kW] 5.5 7.5 8 11
1-phase / 110 V [kW] 0.3 0.75 1.1 1.2 1.6
2 poles 220…240 V [kW] 0.55 1.3 2.2 2.5 3.2
380…440 V [kW] 0.75 2.2 3.7 4.5 5.5