Technical data
Publication 1794-2.1 - January 2000
FLEX I/O and FLEX Integra Product Data
48V dc 16 Sink Input Module Cat. No. 1794-IC16 87
Setting Input Filter Times
This module has a built-in 1ms filter. You can select additional input
filter time (FT) for each group of channels (channels 00 through 11, or
channels 12 through 15). Select the additional input filter time by
setting the corresponding bits in the output image table
(complementary word) for the module.
For example, to set an additional filter of 4ms for a dc input module at
address rack 1, module group 0, set bits 05, 04, 03, 02, 01, and 00 as
shown below. This would result in a total filter time of 5ms.
Input Filter Times
(Standard Addressing Mode Only)
Derating Curve
If maximum voltage is 60, the maximum temperature is 41 (normal) 29 (other).
If maximum voltage is 55, the maximum temperature is 55 (normal) 42 (other).
If maximum voltage is 50, the maximum temperature is 55 (normal) 55 (other).
Bits Description Selected Filter
Time
02 01 00 Filter Time for Inputs 00-11
(00-13)
05 04 03 Filter Time for Inputs 12-15
(14-17)
0 0 0 Filter Time 0 (default) 256µs
0 0 1 Filter Time 1 512µs
0 1 0 Filter Time 2 1ms
0 1 1 Filter Time 3 2ms
1 0 0 Filter Time 4 4ms
1 0 1 Filter Time 5 8ms
1 1 0 Filter Time 6 16ms
1 1 1 Filter Time 7 32ms
Specifications - 1794-IC16
Number of Inputs 16 (1 group of 16), non-isolated, sinking
Module Location Cat. No. 1794-TB3 or -TB3S Terminal Base Unit
Mounting Refer to derating curve
ON-State Voltage 30V dc minimum;
48V dc nominal;
60V dc maximum
ON-State Current 2.0mA minimum;
5.0mA nominal at 48V dc;
11.0mA maximum
OFF-State Voltage 10.0V dc maximum
OFF-State Current 1.5mA minimum
Input Impedance 11K Ω maximum
Isolation Voltage 100% tested at 1900V dc for 1s between user and
system
No isolation between individual channels
Maximum Input
Filter Times
OFF to ON
ON to OFF
Minimum 1ms plus selected filter time of:
256µs, 512µs, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms
256µs, 512µs, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms
256µs default - selectable thru output image table
(see
Setting Input Filter Times
)
Flexbus Current (max) 25mA
Power Dissipation Maximum 6.4W @ 60V dc
Thermal Dissipation Maximum 21.9 BTU/hr @ 60V dc
40843
O:010
Write Filter Time on system startup.
FLL
Fill File
Source 36
Destination#O:010
Length 1
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
100
FT0 = 00-11
Write Filter Time to
complement of input
module.
Dec.=
44 Octal
or 36
Decimal
I:000
00
100
FT1 = 12-15
Indicators (field side
indication, customer
device driven)
16 yellow status indicators
Keyswitch Position 2
General Specifications
External dc Power
Supply Voltage
Voltage Range
Input Supply Current
48V dc nominal
30 to 60V dc (includes 5% ac ripple)
51mA @ 30V
82mA @ 48V
107mA @ 60V
Dimensions HxWxD 46mm x 94mm x 53mm (1.8in x 3.7in x 2.1in)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
0 to 55
o
C (32 to 131
o
F)
-40 to 85
o
C (-40 to 185
o
F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
Conductors Wire Size
Category
12 gauge (4mm
2
) stranded maximum
3/64 inch (1.2mm) insulation maximum
2
1
Publication
Installation Instructions 1794-5.53
Agency Certification
1 Use this conductor category information for planning conductor routing. Refer to
publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines for Noise
Immunity.”
Class I Division 2 certified
Groups A, B, C, D certified
Class I Zone 2 Group IIC certified
4111
9
60
55
50
45
40
35
30
01020304050 6055
V
in
On-state
Voltage
(V dc)
Ambient Temperature
o
C
The area within the curve represents the safe operating range for the module un
d
various conditions of user supplied 48V dc supply voltages and ambient temperat
u
= Normal mounting safe operating range, included
= Other mounting positions (including inverted horizontal) safe
operating range)
29
41
Normal Mounting - Horizontal
Other Mounting (including Vertical and Inverted Horizontal Mounting)
40221