Technical data

Publication 1794-2.1 - January 2000
72 24V dc 8 Source Output Module Cat. No. 1794-OB8 FLEX I/O and FLEX Integra Product Data
Specifications - 1794-OB8
Number of Outputs 8 (1 group of 8) non-isolated, sourcing
Module Location Cat. No. 1794-TB2, -TB3, or -TB3S
Terminal Base Unit
ON-State Voltage Range 10V dc minimum
24V dc nominal;
31.2V dc maximum
ON-State Voltage Drop 0.5V dc maximum
ON-State Current 1.0mA minimum per channel
500mA maximum per channel
OFF-State Voltage 31.2V dc maximum
OFF-State Leakage 0.5mA maximum
Isolation Voltage (min) 100% tested at 850V dc for 1s between user and
system
No isolation between individual channels
Output Signal Delay
OFF to ON
ON to OFF
0.5ms maximum
1.0ms maximum
Flexbus Current (max) 60mA
Power Dissipation 3.3W maximum @ 31.2V
Thermal Dissipation 11.2 BTU/hr @ 31.2V dc
Indicators (field side
indication, logic driven)
8 yellow status indicators
Output Current Rating 4A (8 outputs @ 0.5A)
Surge Current 2A for 50ms, repeatable every 2s
Fusing Module outputs are not fused. Fusing of outputs is
recommended. If fusing is desired, you must
provide external fusing, use SAN-O MQ4-800mA
fuses.
Keyswitch Position 2
General Specifications
External dc Power
Supply Voltage
Voltage Range
Supply Current
24V dc nominal
19.2 to 31.2V dc (includes 5% ac ripple)
25mA @ 24V dc (20 to 35mA)
Dimensions HxWxD 46mm x 94mm x 53mm (1.8in x 3.7 in x 2.1in)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
0 to 55
o
C (32 to 131
o
F)
-40 to 85
o
C (-40 to 185
o
F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
Conductors Wire Size
Category
12 gauge (4mm
2
) stranded maximum
3/64 inch (1.2mm) insulation maximum
2
1
Publication
Installation Instructions 1794-5.31
Agency Certification
1 You use this conductor category information for planning conductor routing as described
in the system level installation manual.
Class I Division 2 certified
Groups A, B, C, D certified
Class I Zone 2 Group IIC certified