Technical data
Publication 1794-2.1 - January 2000
64 24V dc 2 Input/2 Output Combo Module Cat. No. 1793-IB2XOB2P and -IB2XOB2PS FLEX I/O and FLEX Integra Product Data
Example of 2-Wire and 3-Wire Sensors
Setting Input Filter Time
(Standard Addressing Mode Only)
(not available when used with the 1794-ASB adapter)
You can select the input filter time (FT) for channels 00 and 01. Select
the input filter time by setting the corresponding bits in the
configuration word (word 3) for the module.
For example, to set a filter time of 4ms for an input module at address
rack 1, module group 0, set bits 02, 01, and 00 as shown below.
Input
1
Input Type Input Terminal Supply Terminal
0 Sink Input 2 1
1 Sink Input 3 6
Output Output Type Output Terminal Common
0
Source Output
412
1
Source Output
513
+24V dc Terminals 1, 6, 8, 9, 14, 15 are internally connected together in the
module.
24V dc
common
Terminals 0, 7, 10 thru 13 are internally connected together in the
module
1 Two wire devices use input, supply terminals, 3-wire devices use input, supply and
common.
Bits Description Selected Filter
Time
02 01 00 Filter Time for Inputs 00-07
0 0 0 Filter Time 0 (default) 256µs
0 0 1 Filter Time 1 512µs
0 1 0 Filter Time 2 1ms
0 1 1 Filter Time 3 2ms
1 0 0 Filter Time 4 4ms
1 0 1 Filter Time 5 8ms
1 1 0 Filter Time 6 16ms
1 1 1 Filter Time 7 32ms
0
7
8
15
123456
9 10 11121314
3-wire sensor
2-wire sensor
41338
40609
O:010
Write Filter Time on system startup.
FLL
Fill File
Source 4
Destination #O:010
Length 1
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
100
FT = 00-07
Write Filter Time Constant to complement of input module.
Dec.=4
Octal or 4
Decimal
I:000
00
Specifications - 1793-IB2XOB2P and -IB2XOB2PS
Number of Channels 2 digital input - sinking
2 digital output - sourcing, protected
Module Location DIN-rail mounted
Module Type 2 input/2 output digital combination with electronic
fusing
1793-IB2XOB2P - screw-clamp terminations
1793-IB2XOB2PS - spring-clamp terminations
Input
ON-State Voltage 10-31.2V dc; 24V dc nominal
ON-State Current 2-12mA; 8mA @ 24V dc
OFF-State Voltage 5.0V dc maximum
OFF-State Current 1.5mA minimum
Channel Impedance 4.6K Ω
Dielectric Withstand Test Channel to system - 850V dc for 1s
Channel to channel - none
Maximum Input
Filter Times
OFF to ON
ON to OFF
256µs, 512µs, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms
256µs, 512µs, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms
256µs default - selectable thru output image table
(see
Setting Input Delay Times
)
Output
On-State Voltage 10-31.2 V dc; 24V dc nominal
On-State Current 1-500mA per channel
Off-State Voltage 31.2V dc maximum
Off-State Current 0.5mA maximum leakage
Channel Impedance 1.0Ω (0.5V dc maximum drop)
Surge Current 1.5A for 50ms, repeatable every 2s
Dielectric Withstand Test Channel to system - 850V dc for 1s
Channel to channel - none
Maximum Input Delay Times
OFF to ON
ON to OFF
0.5ms maximum
1.0ms maximum
General Specifications
Flexbus Current 20mA maximum
Power Dissipation 1.4W @ 31.2V dc
Thermal Dissipation 4.8 BTU/hr @ 31.2V dc
Indicators 4 yellow channel status indicators
Fusing Output are electronically fused
External dc Power
Voltage
Current
19.2-31.2V dc (5% ac ripple)
40mA maximum
Dimensions HxWxD 69mm x 55mm x 80mm
(2.72in x 2.17in x 3.15in)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
0 to 55
o
C (32 to 131
o
F)
-40 to 85
o
C (-40 to 185
o
F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
Conductors Wire Size
Category
12 gauge (4mm
2
) stranded maximum
3/64 inch (1.2mm) maximum insulation, 90
o
C
minimum temperature rating
2
1
Terminal Screw Torque 4-7 inch-pounds
Publication
Installation Instructions 1793-5.3
Agency Certification
1 Use this conductor category information for planning conductor routing. Refer to pub
1770-4.1, “Industrial Automation Wiring and Grounding Guidelines for Noise Immunity.”